SITE MAP
 
 
Home | Products | Company | Reference | Worldwide | | Contact
 
 
    PRODUCTS  
Product Information > UPS > Pyramid DSP > Technical Specifications  
MODEL(380-400-415V 3ph version) PDSP33120 PDSP33160 PDSP33200 PDSP33250 PDSP33300
Output Power (kVA) 120 160 200 250 300
Nominal Active Power (kW) 96 128 160 200 240
MODEL(200-208-220V 3ph version) PDSP-U33060 PDSP-U33080 PDSP-U33100 PDSP-U33125 PDSP-U33150
Output Power (kVA) 60 80 100 125 150
Nominal Active Power (kW) 48 64 80 100 120
INPUT  
Number of phases 3Ph + N + PE
Nominal Voltage (Ph-Ph) 200V/208V/220V (PDSP-U)
380V/400V/415V (PDSP)
Voltage Range (100% load) (Ph-N) (-15)%(+27)%
Voltage Range (64% load) (Ph-N) (-45)%(+27)%
Voltage Range (42% load) (Ph-N) (-64)%(+27)%
Nominal Frequency (Hz) 50 or 60
Frequency range for online operation ±10%
Input Current THD ≤4%(*)
Input Power Factor 0,99
OUTPUT  

Power Factor

0.8
Number of phases 3Ph+N+PE(PDSP&PDSP-U)
Voltage
(3ph_Phase to Phase)
200V/208V/220V (PDSP-U) or
380V/400V/415V (PDSP)
Static Voltage Regulation at %100 Linear Load (online&battery mode) <1%
Voltage THD at rated linear load <3%
Crest Factor 3 : 1
Frequency (Hz) 50 or 60
Free Running Frequency (Hz) ± 0.01%
Overload 125% for 10 minutes , 150% for 1 minute
Efficiency up to 95% (**)
BATTERY  
Type Maintenance-free lead acid batteries
Quantity (pcs)
PDSP version
62 (2*31) 60 (2*30)
Quantity (pcs)
PDSP-U version
34 (2*17)
Battery Protection Deep Discharge Protection with Auto Cut off
Battery Test Standard (Automatic and Manual)
DISPLAY  
LED Display Line, Bypass, Battery, Inverter, Load, Fault Indications
LCD Display Load%, Input&Output Frequency, Voltage&Current, Bypass voltage, Battery Voltage & current, Temperature, Alarms
STATIC BYPASS  
Number of phases 3PH+N+PE
Voltage Range for bypass operation ±10%
Frequency Range for bypass operation (Hz) ±6% (Configurable)
COMMUNICATION  
Interface (Communication Ports) RS232&RS422
Dry Contact Signals AC failure, Battery under voltage, bypass operation, output failure
Others EPO, Generator interface
ENVIRONMENT  
Storage Temperature Range (°C ) -25 to +55 ( 15 to 40 recomended for longer battery life time )
Operating Temperature Range (°C ) 0 to 40 ( 20 to 25 recomended for longer battery life time )
Relative Humidity Range 0-95% (non-condensing)
Maximum Altitude without derating (m) 1000
Protection Level IP 20
PYSICAL SPECIFICATIONS  
Dimensions wxdxh (cm) 77x76x168 96x87x186 161x108x193
Weight (kg) 330 370 380 740 765
Product Certification CE
STANDARDS
Standards EN 62040-1-1 (safety), EN 62040-2 (EMC), EN 62040-3 (VFI-SS-111)
(*) for source having THDv <2 % @ nominal load
(**) varies depending on ups power
(!) 50/60 Hz Frequency Converter Versions are available
 
©Copyright 2007, All Rights Reserved, - Inform Elektronik San. ve Tic. A.Þ. 3NOKTA