| MODEL |
PPS 310 |
PPS 315 |
PPS 320 |
PPS 330 |
PPS 340 |
PPS 360 |
PPS 380 |
PPS 3100 |
PPS 3120 |
PPS 3160 |
PPS 3200 |
PPS 3250 |
PPS 3300 |
| Output Power kVA |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
100 |
120 |
160 |
200 |
250 |
300 |
| Power Factor |
0.8 lagging |
| INPUT |
|
| Voltage |
380V / 400V / 415V 3 phase |
| Tolerance |
±15% |
| Frequency |
50 / 60Hz |
| Tolerance |
±10% |
| OUTPUT |
|
| Power Factor |
0.8 |
| Voltage |
380V / 400V / 415V 3 phase |
| Tolerance (static condition) |
± 1% |
| Tolerance (dynamic condition) |
± 5% |
| Harmonic Distortion rate |
<3% |
| On Linear Load |
| Harmonic Distortion rate |
<5% |
| on non-linear load |
| Crest Factor |
3 |
| Frequency |
50 or 60 Hz |
| Frequency Tolerance |
± 0.2% |
| Overload |
|
| 100% - 125% load |
10 min |
| 125% - 150% load |
1 min |
| Overall Efficiency |
>=90% |
| BATTERY |
|
| Type |
Maintenance-free lead acid batteries |
| Quantity |
30pcs 12V Batteries |
32pcs 12V Batteries |
| DISPLAY |
|
| LED Display |
Line, Battery,Bypass,Inverter,Maintenance switch,output switch indicators |
| LCD Display |
Load%, Output voltage&frequency, Input and bypass voltages, Battery voltage and current, Temperature, Alarm messages |
| COMMUNICATION |
|
| Interface(Communication Ports) |
RS 232 |
| Dry Contact Signals |
Line Failure, battery low, load on by-pass, battery CB input, battery CB output, emergency stop input |
| PHYSICAL |
|
| Weight without battery (kg) |
225 |
255 |
270 |
285 |
400 |
475 |
655 |
815 |
940 |
965 |
1170 |
1465 |
1535 |
| Dimensions (mm) W×D×H |
490×650×1190 |
565×860×1400 |
720x820x1450 |
1120×820×1650 |
1200x860x1730 |
1590x950x1900 |
| ENVIRONMENT |
|
| Audible Noise |
<55dBA |
<60dBA |
63 to 66dBA |
<70dBA |
| Operating Temperature |
0-40°C |
| Relative Humidity (non condensing) |
0-95% |
| Protection Level |
IP 20 |
| STANDARDS |
|
|
EN 62040-11 (safety), EN 62040-2 (EMC) |