| MODEL |
GUARDIAN 600A/AP |
GUARDIAN 650A/AP |
GUARDIAN 800A/AP |
GUARDIAN 1000A/AP |
GUARDIAN 1500A/AP |
GUARDIAN 2000A/AP |
GUARDIAN LCD 600A/AP |
GUARDIAN LCD 650A/AP |
GUARDIAN LCD 800A/AP |
GUARDIAN LCD 1000A/AP |
GUARDIAN LCD 1500A/AP |
GUARDIAN LCD 2000A/AP |
| INPUT |
|
|
|
|
|
|
| Capacity (VA) |
600 |
650 |
800 |
1000 |
1500 |
2000 |
| Voltage |
220V or 230V |
| Input Voltage Range |
-25%, +30% |
| Frequency |
50 or 60 Hz (auto sensing) |
| OUTPUT |
|
| Power Factor |
0.6 |
| Voltage (On battery) |
220V or 230V ±10% |
| Waveform (On battery) |
Simulated Sinewave |
| Frequency (On battery) |
50 or 60 Hz ±1Hz |
| Voltage Regulation (AVR) |
AVR automatically increases output voltage 15% above input voltage if -10% to -26% of nominal
AVR automatically decreases output voltage 15% below input voltage if +10% to +22% of nominal |
| Transfer Time |
2 - 6 ms. |
| Outlets |
1pcs Schuko 1pcs IEC |
2pcs Schuko 2pcs IEC |
| BATTERY |
|
| Type |
Maintanence - Free lead acid batteries |
| Recharge Time |
6 hours (to 90% of full capacity) |
| Voltage |
12 VDC |
24 VDC |
| Back up time |
5-30 minutes (depending on computer load) |
| DISPLAY |
|
| LED Display |
Fault, Battery Mode, AC Mode |
LCD Display (for Guardian LCD) |
Input&Output voltage values, AC mode/Load Level/Battery Capacity Indicators |
| PROTECTION |
|
|
Short Circuit, Overload, Battery Discharge, Overcharge, Tel/Phone line (AP Models only) |
| COMMUNICATION |
|
| Communication Interface |
USB port (only AP models) |
| AUIDIBLE ALARMS |
|
|
Battery Mode (every 10 seconds), Low Battery (every second), Overload (every 0.5 second) Battery Replacement (every 2 seconds), Fault (Continous) |
| ENVIRONMENT |
|
| Operating Temp. |
0-40 °C |
| Humidity |
0 to 90% non-condensing |
| Audible Noise |
<40dBA |
| Protection Class |
IP20 |
| PHYSICAL |
|
| Net Weight(kg) |
4 |
4,25 |
4,9 |
8 |
11,1 |
11,5 |
| Dimensions (mm) DxWxH |
100x287x142 |
146x350x160 |
146x397x205 |
| STANDARDS |
|
| Standards |
EN 62040-1-1 (safety), EN 62040-2 (EMC) |