| MODEL |
24VDC Input |
48VDC Input |
110 VDC Input |
| Model |
INV1524 |
INV2524 |
INV2048 |
INV3048 |
INV5048 |
INV20110 |
INV30110 |
INV50110 |
INV100110 |
| Power(VA) |
1500VA |
2500VA |
2000VA |
3000VA |
5000VA |
2000VA |
3000VA |
5000VA |
10000VA |
| INPUT |
|
| DC Input Voltage |
20-40 VDC |
40-80 VDC |
90-140 VDC |
| DC Input Current (maximum) |
75A |
121A |
48A |
71A |
120A |
21A |
29A |
50A |
97A |
| OUTPUT |
|
Output Voltage (adjustable ±5%) |
230VAC |
| Output Current |
6,5A |
10,8A |
8,7A |
13,0A |
21,7A |
8,7A |
13,0A |
21,7A |
43,5A |
| Output Frequency (selectable) |
50/60 Hz |
| Crest Factor |
2,5:1
| 2:1
| 3:1
| 2:1
| 2:1
| 3:1 |
| Surge Capacity for 5 seconds |
9A |
12A |
16A |
24A |
25A |
39A |
63A |
| Power Factor |
0.75 |
| Voltage THD (@lineer load) |
<3% |
| Effiency (optimum) |
>84% |
>85% |
>86% |
>89% |
>90% |
>91% |
>92% |
| DISPLAY |
|
| LCD Display |
2x16 character LCD Display |
| Indicators |
Output Ok, Input Ok, Common alarm LEDs |
| ALARMS&PROTECTIONS |
|
| Alarms&Protection |
Output&Input fuse, DC Undervoltage&Overvoltage, Overload, Short Circuit&IPM Fault, Over Temperature |
| ENVIRONMENT |
|
| Operation Temperature |
0°C-60°C |
| Storage Temperature |
(-20°C)...(+70°C) |
| Relative Humidity (non condensing) |
0-90% |
| Cooling Method |
Forced FAN cooling |
| Protection Class |
IP20 |
|