MODULAR DSP POWER FRAMES |
| MODEL |
MD-60 |
MD-80 |
BATMD-120 |
| Output Power KW |
60KW |
80KW |
-- |
| UPS Modules (max.) |
3pcs. |
4pcs. |
Battery Only |
| Inbuilt Batteries |
Yes |
Yes |
Yes |
| Dimensions (cm) |
19'' 36U 1000mm |
19'' 42U 1000mm |
19'' 42U 1000mm |
| Weight (kg) w/o modules |
130 |
145 |
145 |
|
MODULAR DSP POWER MODULES |
| Topology |
Online double Conversion (VFI-SS-111) |
| Operation Type |
Real Current Sharing Parallel Redundant |
| Max. Parallel Modules |
8pcs |
| Nominal Output Power |
20 kVA ( 20kW ) per module |
| INPUT |
|
| Voltage |
380V / 400V / 415V 3 Phase+N+G |
| Tolerance @full load |
± 20% |
| Tolerance @half load |
+20%...-40% |
| Frequency |
50/60Hz |
| Tolerance |
±10% |
| Power Factor |
0.99 |
| Current Harmonic Distortion (THDi) |
<4% |
| Max. inrush current at start up |
<45Amp |
| OUTPUT |
|
| Power |
20 kVA (20kW) |
| Power Factor |
1 |
| Voltage |
380V/400V/415V 3Phase+N+G |
| Tolerance(static condition) |
±1% |
| Tolerance(dinamic condition) |
±3% |
| Total Output Voltage Distortion rate on lineer load |
<3% |
| Total Output Voltage Distortion rate on non-lineer load |
<5% |
| Crest Factor |
3:1 |
| Frequency |
50 or 60 Hz |
| Frequency Tolerance |
±0.01% |
Overload 100%-125% load 125%-150% load |
10min. 1min. |
| Overall Efficiency |
up to 93% |
| Green Mode Efficiency |
up to 97% |
| BYPASS |
|
| Frequency Variation Speed |
<1Hz/sec |
| Voltage Tolerance |
±15% |
| Frequency |
50 or 60 Hz |
| Frequency Tolerance |
±2% |
| BATTERY |
|
| Type |
Maintenance-free lead acid or NiCd batteries |
| Quantity |
28pcs...32pcs (configurable) |
| DISPLAY |
|
|
LCD Graphical Touch Screen |
| COMMUNICATION |
|
| Interface (Communication Ports) |
RS232 Communication port and EPO as standard |
|
USB Port, SNMP, Dry Contact board (optional) |
| PHYSICAL SPECIFICATIONS |
|
Weight Without Battery (kg) |
60 |
| Dimensions (mm) WxDxH |
440x660x265 - 6U |
| ENVIRONMENT |
|
| Audible Noise |
<55dBA |
| Operating Temperature |
0-40 °C |
| Relative Humidity (non condensing) |
0-95% |
| Protection Level |
IP20 |
| STANDARDS |
|
|
EN 62040-1-1 (safety), EN 62040-2(EMC), EN 62040-3 (Performance) |