| MODEL |
PDS 500 |
PDS 600 |
PDS 800 |
PDS 1000 |
| Output Power (kVA) |
500 |
600 |
800 |
1000 |
| Output Power (kW) |
400 |
480 |
640 |
800 |
| INPUT |
|
| Voltage |
380V / 400V / 415V 3 Phase+Neutral+PE |
| Tolerance |
± 15% |
| Frequency |
50 - 60 Hz |
| Tolerance |
± 10% |
| DC Ripple Voltage |
± 1% |
| DC Ripple Current |
max 2% of battery capacity defined in Amps |
| OUTPUT |
|
| Power Factor |
0.8 |
| Voltage |
380V / 400V / 415V 3 Phase+Neutral+PE |
Tolerance static condition step load (0%-100%-0%) step load (0%-50%-0%) |
±1% ±8% recovering within tolerance into 2 cycles ±3% recovering within tolerance into 2 cycles |
| Total Harmonic Distortion |
< 2% (@ 100% linear load) |
| Crest Factor |
3:1 with 80% load |
| Frequency |
50 or 60 Hz. |
| Frequency tolerance (free running) |
± 0.01% |
| Frequency tolerance (synchronized with utility) |
±5% |
Overload 125% load 150% load |
10 min 1 min |
| Overall Efficiency |
0.925 |
| Output Neutral Rating |
2 |
| BATTERY |
|
| Type |
Maintenance-free lead acid batteries |
| Quantity |
32 pcs 12V Blocks |
| Nominal DC Voltage |
384VDC |
| Float Voltage at 20C |
436VDC |
| Automatic and Manual Battery Test |
Standard |
| STATIC BYPASS |
|
| Input Configuration |
Common with Rectifier or Seperate |
| Transfer Limits |
± 10% of Nominal Adjusted Output Voltage |
| Overload Capability |
Continous at 110% |
| Short Circuit Capability |
5min @ 200% and half cycle @ 1000% (non repetitive) |
| ENVIRONMENT |
|
| Audible Noise |
<68dBA |
<70dBA |
| Operating Temperature |
0-40°C |
| Relative Humidity (non condensing) |
0-95% |
| Protection Class |
IP 20 |
| PHYSICAL SPECIFICATIONS |
|
Weight Without Battery (kg) |
2900 |
3100 |
3800 |
4000 |
| Dimensions (mm) WxDxH |
3400*1000*1800 |
3400*1400*1800 |
4200*1400*1800 |
| STANDARDS |
|
|
EN 62040-1-1 (safety), EN 62040-2(EMC), EN 62040-3 (VFI-SS-111) |