| MODEL |
SS 210 |
SS 220 |
SS 230 |
| INPUT |
|
| Power (kVA) |
1 |
2 |
3 |
| Voltage |
160 - 280 VAC |
| Frequency |
50 / 60 Hz. ± 5 % |
| Power Factor |
>0.98 |
| OUTPUT |
|
| Output Power Factor |
0.7 |
| Voltage |
220VAC / 230VAC |
| Voltage Regulation |
±%2 |
| Frequency |
50 / 60 Hz (Auto Detection) |
| Frequency Regulation |
±0,5% |
| Harmonic Distortion |
< 3 % (For Linaer Loads) |
| Crest Factor |
3:1 |
| Overload Capacity |
100% - 120% for 60 seconds, 120% - 150% for 10 seconds |
| Whole efficiency |
>85% |
| Inverter efficiency |
>90% |
| Transfer Time |
0ms |
| Outlets |
3pcs IEC & 1pc Schuko Outlets |
3pcs IEC & 2pcs Schuko Outlets |
6pcs IEC & 2pcs Schuko Outlets |
| BATTERY |
|
| Type |
Maintenance-free lead acid batteries |
Recharge Time
Voltage |
8 hours (to 90% of full capacity) |
| 36VDC |
72VDC |
96VDC |
| Quantity |
3 pcs 12V 7ah |
6 pcs 12V 7ah |
8 pcs 12V 7ah |
| Back Up Time Full Load |
8 min |
7 min |
| Half Load |
20 min |
15 min |
| DISPLAY |
|
| LED Display |
line input, inverter, bypass, fault, overload, battery low, self-test, Load/Battery Level |
| ALARMS |
|
| |
Line Failure, Battery Low, Transfer To Bypass, Failure Events |
| PROTECTION |
|
|
short circuit, over temperature, overload, high voltage, battery low |
| COMMUNICATION |
|
Interface (Communication Port) |
RS-232 |
| Monitoring and Management Software |
standard |
| ENVIRONMENT |
|
| Temparature |
0°C - 40°C |
| Humidity |
0%-95% |
| Noise Level (1m Distance) |
<45dBA |
| Protection Class |
IP20 |
| PHYSICAL SPECIFICATIONS |
|
| Tower Type |
|
| Net Weight(kg) |
15 |
29 |
35 |
| Dimensions (mm) WxHxD |
147x401x223 |
130x475x360 |
190x450x360 |
| 19" Rack Mount Type |
|
| Net Weight(kg) |
16 |
28 |
37 |
| Dimensions (mm) WxHxD |
483x390x88 |
483x485x130 |
483x460x192 |
| STANDARDS |
|
| Standards |
EN 62040-1-1 (safety), EN 62040-2 (EMC) |